Product Code: CEI-CFSD / CFSD-M
Combined Fire & Smoke Dampers
صمامات حريق ودخان مدمجة
Dual-function dampers providing both fire and smoke containment in a single assembly. Fusible link fire closure combined with electric smoke actuator. Reduces installation complexity and cost.
Frame Material
Quick Query?
WhatsApp Us →
ISO 9001:2015SMACNADW144
Description
Product Description
Castle Combined Fire & Smoke Dampers perform dual function — both fire damper (UL 555) and smoke damper (UL 555S) in a single unit. Spring-return motorized actuator with 72°C thermal fusible link as backup. Provides fire compartmentation AND smoke control at duct penetrations through fire-rated barriers — eliminating the need for separate fire and smoke dampers.
Dual Certified
Single unit meets both UL 555 (fire) AND UL 555S (smoke) — eliminates need for two separate dampers.
Triple Protection
Motor closes on smoke signal + thermal link activates on heat + spring closes on power loss.
Space Saving
One damper instead of two — reduces installation space, cost and maintenance requirements.
Dynamic Rated
Closes against 2000 fpm airflow — system can remain running during fire event.
ISO 9001:2015 Certified
Quality management system certified by IGC, covering all stages from raw material to final delivery.
SMACNA & DW144 Compliant
Manufactured to the latest edition of SMACNA HVAC Duct Construction Standards and DW144.
Custom Sizes Available
Non-standard dimensions manufactured to project specifications with competitive lead times.
Approved by Leading Consultants
Accepted by Dar Al-Handasa, ECG, SYSTRA, Khatib & Alami and 25+ major engineering consultants.
Specifications
Technical Specifications
| Parameter | Value | Unit |
|---|---|---|
| Frame Material | Galvanized steel 1.5mm minimum | — |
| Blade Material | Galvanized steel — multi-blade opposed | — |
| Actuator | Spring-return fail-safe + thermal fusible link 72°C | — |
| Fire Rating | 1.5 hour / 3.0 hour (UL 555) | hours |
| Smoke Rating | ES 60/120 min (UL 555S / BS EN 1366-10) | min |
| Leakage Class | Class I or Class II per UL 555S | — |
| Control Signal | 24V/230V — On/Off / BACnet / Modbus | — |
| Max Velocity | 2000 fpm (10 m/s) dynamic rated | m/s |
| Rectangular Sizes | 150×150 to 1500×1500mm | mm |
| Blade Seal | SS jamb seals + silicone blade edge seals | — |
| Installation | Vertical or horizontal — wall or floor | — |
| Compliance | UL 555 + UL 555S / BS EN 1366-2 + 1366-10 / NFPA 90A | — |
Applications
Fields of Application
Fire & smoke rated wall penetrations
Fire & smoke rated floor penetrations
Critical facility compartmentation
Hospital and healthcare barriers
High-rise building duct shafts
Data center fire barriers
Quality Assurance
Tests & Certificates
Duct Test
Rigorous leakage and pressure testing to SMACNA and DW144 standards.

Duct Test 01

Duct Test 02

Duct Test 03
Air Tests
Air velocity and distribution testing.

Air Test 01