🛠️ Outil Ingénierie · Gratuit

Calculateur de Gaines

Calculez les dimensions des gaines CVC rondes et rectangulaires selon la méthode de friction égale — la norme ASHRAE. Résultats instantanés, sans inscription.

✓ Conforme ASHRAE ✓ Impérial & Métrique ✓ Rond & Rectangulaire
Paramètres d'Entrée
CFM
in.wg/100ft
Method: Equal Friction (ASHRAE, SMACNA) · Standard air (0.075 lb/ft³, 20°C)
RECTANGULAIRE ROND
Prêt à dimensionner votre gaine?
Entrez le débit (CFM) et appuyez sur Calculer — vous obtiendrez les options rondes et rectangulaires.
How does the Equal Friction Method work?

The Equal Friction Method sizes all ducts in a system to have the same friction loss per unit length (typically 0.08–0.10 in.wg per 100 ft). This ensures a self-balancing system with predictable pressure drops.

The friction loss for round duct is calculated using the ASHRAE simplified equation:

Δp = 0.109136 × Q1.9 / D5.02

Where Δp = friction (in.wg/100 ft), Q = airflow (CFM), D = diameter (in).

Recommended Vitesse Ranges (Supply Air)
ApplicationMain DuctBranch Duct
Résidentiel700–900 fpm600 fpm
Commercial (offices)1200–1500 fpm800–1000 fpm
Public / Retail1500–1800 fpm1000–1300 fpm
Industrial1800–2500 fpm1500–2000 fpm
Hospital / Studio800–1200 fpm600–800 fpm
Round vs Rectangular — Which to choose?

Round ducts are more efficient — up to 30% less friction loss for the same airflow. They're preferred where space allows.

Rectangular ducts fit better in tight ceiling spaces and are easier to seal at joints. Aspect ratios above 4:1 are discouraged because they lose efficiency and are harder to fabricate rigidly.

Castle Engineering fabricates both to SMACNA and DW144 standards.

Disclaimer

This tool provides estimates based on standard air properties (0.075 lb/ft³ at 20°C, sea level) and clean galvanized steel ductwork. For non-standard air (high temperature, altitude, humidity), duct roughness other than galvanized steel, or complex systems requiring detailed calculation, please consult a licensed HVAC engineer.